Description
Discontinued on: 15 January 2023
To be end-of-service on: 31 December 2030
Recommended replacement(s):
Schneider Electric BMXART0814 analog isolated low level input module, Modicon X80, 8 inputs, 40mV positive or negative
BMXART0814
Range of Product | Modicon Quantum automation platform |
---|---|
Product or Component Type | Analogue input module |
Type of filter | Notch filter - 3 dB at 50/60 Hz Single pole low pass - 3 dB at 20 Hz |
Analogue input number | 8 |
---|---|
Addressing requirement | 10 input words |
Analogue input type | Thermocouple - 270...1000 °C thermocouple E Thermocouple - 270...1370 °C thermocouple K Thermocouple - 270...400 °C thermocouple T Thermocouple - 50...1665 °C thermocouple R Thermocouple - 50...1665 °C thermocouple S |
16 bits | |
Absolute accuracy error | +/- 2 °C plus + 0.1 % of reading thermocouple E +/- 2 °C plus + 0.1 % of reading thermocouple J +/- 2 °C plus + 0.1 % of reading thermocouple K +/- 2 °C plus + 0.1 % of reading thermocouple T +/- 4 °C plus + 0.1 % of reading thermocouple R +/- 4 °C plus + 0.1 % of reading thermocouple S |
Linearity error | 1 °C, 0.1 °C, 1 F, 0.1 F - 210...760 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 270...1000 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 270...1370 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 270...400 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 50...1665 °C |
Accuracy drift according to temperature | 0.15 µV/°C + 0.0015 % of reading/°C max low level voltage |
Common mode rejection | > - 120 dB 50/60 Hz |
Isolation between channels and bus | 1780 V AC 60 s 2500 V DC 60 s |
Isolation between channels | 300 V DC 220 V AC |
Update time | 1000 ms |
Fault type | Broken wire Overtacking scale |
Marking | CE |
Cold junction compensation | Internal 32…140 °F (0…60 °C) |
Local signalling | For bus communication is present (Active) 1 LED (green) for external fault 1 LED (red) for channel is turned on 8 LEDs (green) for channel fault 8 LEDs (red) |
Bus current requirement | 280 mA |
Power dissipation in W | 1.5 W |
Module format | Standard |
Net Weight | 0.66 lb(US) (0.3 kg) |
Environment
Standards | CSA C22.2 No 142 UL 508 |
---|---|
Product Certifications | CUL FM Class 1 Division 2 |
Resistance to electrostatic discharge | 4 kV contact IEC 801-2 8 kV on air IEC 801-2 |
Resistance to electromagnetic fields | 9.14 V/m (10 V/m) 80…1000 MHz IEC 801-3 |
Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
Relative Humidity | 95 % without condensation |
Operating altitude | <= 16404.2 ft (5000 m) |
Ordering and shipping details
Category | 18155-QUANTUM I/O & POWER SUPPLIES |
---|---|
Discount Schedule | PC21 |
GTIN | 3595861126602 |
Returnability | No |
Country of origin | FR |
Packing Units
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 1.97 in (5.000 cm) |
Package 1 Width | 6.50 in (16.500 cm) |
Package 1 Length | 12.40 in (31.500 cm) |
Package 1 Weight | 14.99 oz (425.000 g) |
MANUFACTURERS
Price history
As soon as the price of the products decreases, you will immediately know about it.