Beckhoff EK1110 EtherCAT extension

$165.00
EK1110
12 in stock
+

The EK1110 EtherCAT extension is placed at the end of an EtherCAT Terminal segment or an Embedded PC from the CX series and offers the option of extending the EtherCAT network in the form of a line topology.

Special features:

  • Connection technology: 1 x RJ45 socket
  • Connection lengths: up to 100 m
  • Extension of an EtherCAT network in line topology

The EK1110 has an RJ45 socket that enables connection of an Ethernet cable with RJ45 connector and establishes a connection to a further EtherCAT segment or to individual EtherCAT devices. The E-bus signals are converted to 100BASE-TX Ethernet signal representation in a continuous process. Power supply to the EK1110 electronics is via the E-bus. No parameterization or configuration is required.


Technical dataEK1110
Task within EtherCAT systemconversion of the E-bus signals to 100BASE-TX Ethernet for extension of the EtherCAT network
Data transfer mediumEthernet/EtherCAT cable (min. Cat.5), shielded
Distance between stations100 m (100BASE-TX)
Protocolany EtherCAT protocol
Delayapprox. 1 µs
Data transfer rates100 Mbit/s
Configurationnot required
Bus interface1 x RJ45
Power supplyfrom E-bus
Current consumption E-bustyp. 130 mA
Electrical isolation500 V (supply voltage/Ethernet)
Weightapprox. 50 g
Operating/storage temperature-25…+60 °C/-40…+85 °C
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Relative humidity95 %, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL, ATEX
Ex markingII 3 G Ex nA IIC T4 Gc

Housing dataEK-44-8pin
Design formcompact terminal housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)44 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxx series
Wiringsolid conductor (e), flexible conductor (f) and ferrule (a): spring actuation by screwdriver
Connection cross-sections*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm²
Connection cross-section AWGs*: AWG 28…14,
st*: AWG 28…14,
f*: AWG 26…16
Stripping length8…9 mm
Current load power contactsImax: 10 A

*s: solid wire; st: stranded wire; f: with ferrule