Description
The EL2008 digital output terminal connects the binary 24 V DC control signals from the automation device on to the actuators at the process level with electrical isolation. Each EtherCAT Terminal has eight channels that indicate their signal state via light emitting diodes.
Special features:
- Connection of different load types possible (ohmic, inductive, lamp load)
- Max. output current 0.5 A per channel
- Short-circuit-proof outputs and reverse polarity protection
Technical data | EL2008, ES2008 |
---|---|
Connection technology | 1-wire |
Number of outputs | 8 |
Nominal voltage | 24 V DC (-15 %/+20 %) |
Load type | ohmic, inductive, lamp load |
Distributed clocks | – |
Max. output current | 0.5 A (short-circuit proof) per channel |
Short-circuit current | typ. < 2 A |
Reverse voltage protection | yes |
Breaking energy | < 150 mJ/channel |
Switching times | typ. TON: 60 µs, typ. TOFF: 300 µs |
Current consumption E-bus | typ. 110 mA |
Electrical isolation | 500 V (E-bus/field potential) |
Current consumption power contacts | typ. 15 mA + load |
Bit width in the process image | 8 outputs |
Configuration | no address or configuration setting |
Weight | approx. 55 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/see documentation |
Pluggable wiring | for all ESxxxx terminals |
Approvals/markings | CE, UL, ATEX, DNV GL, IECEx, cFMus |
Ex marking | ATEX: II 3 G Ex nA IIC T4 Gc IECEx: Ex nA IIC T4 Gc Ex tc IIIC T135 °C Dc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |