Description
The job of the EL3142 analog input terminal is to supply power to measuring transducers located in the field, and to transmit analog measurement signals with electrical isolation to the automation device. The voltage for the sensors is supplied to the terminals via the power contacts. The power contacts can optionally be supplied with operating voltage in the standard way or via a supply terminal (EL9xxx) with electrical isolation. The input electronics is independent of the supply voltage of the power contacts. The 0 V power contact is the reference potential for the inputs. The EtherCAT Terminal indicates its signal state by means of light emitting diodes.
Technical data | EL3142 |
---|---|
Number of inputs | 2 (single-ended) |
Power supply | via the E-bus |
Technology | single-ended |
Signal current | 0…20 mA |
Oversampling factor | – |
Distributed clocks | yes |
Distributed clock precision | << 1 µs |
Internal resistance | typ. 85 Ω + diode voltage |
Input filter limit frequency | 5 kHz |
Resolution | 16 bit (incl. sign) |
Conversion time | ~ 60 µs (fast mode ~ 40 µs) |
Input signal bandwidth | see input filter |
Measurement error/ uncertainty | < ±0.3 % (relative to full scale value) |
Electrical isolation | 500 V (E-bus/signal voltage) |
Current consumption power contacts | – |
Current consumption E-bus | typ. 170 mA |
Dielectric strength | max. 30 V |
Bit width in the process image | inputs: 8 byte |
Special features | standard and compact process image, activatable FIR/IIR filters, limit value monitoring |
Weight | approx. 60 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Relative humidity | 95 %, no condensation |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
Protect. rating/installation pos. | IP20/variable |
Pluggable wiring | for all ESxxxx terminals |
Approvals/markings | CE, UL, ATEX |
Ex marking | II 3 G Ex nA IIC T4 Gc |
Housing data | EL-12-8pin | ES-12-8pin |
---|---|---|
Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
Material | polycarbonate | |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
Side by side mounting by means of | double slot and key connection | |
Marking | labeling of the BZxxx series | |
Wiring | solid conductor (e), flexible conductor (f) and ferrule (a): spring actuation by screwdriver | |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG 28…14, st*: AWG 28…14, f*: AWG 26…16 | s*: AWG 28…16, st*: AWG 28…16, f*: AWG 26…16 |
Stripping length | 8…9 mm | 9…10 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule
MANUFACTURERS
Price history
The price has not changed yet. We will show it on this chart once it changes