Beckhoff EL3314 EtherCAT Terminal, 4-channel analog input, temperature, thermocouple, 16 bit

Brand:BECKHOFF, Condition:new
$315.00
EL3314
2 in stock (more units ~3 weeks)
+

Description

The EL3314 analog input terminal allows four thermocouples to be connected directly. The EtherCAT Terminal circuit can operate thermocouple sensors using the 2-wire technique. A microprocessor handles linearization across the whole temperature range, which is freely selectable. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminal. The EL3314 can also be used for mV measurement.


echnical dataEL3314
Number of inputs4
TechnologyTemperature measurement (TC)
Connection method2-wire
Signal typedifferential
Temperature measurement (thermocouple)type B, C, E, J, K, L, N, R, S, T, U (default setting: type K)
Measurement uncertainty (temperature measurement)at 23 °C ambient temperature, with internal cold junction, according type: B: ±8.5 °C; C: ±6.2 °C; E: ±2.5 °C; J: ±2.7 °C; K: ±3 °C; L: ±2.3 °C; N: ±3 °C; R: ±6.7 °C; S: ±7.1 °C; T: ±2.9 °C; U: ±2.5 °C; for further details see documentation
Voltage measurement±30/±60/±75 mV
Measurement uncertainty (voltage measurement)at ±75 mV, 23 °C ambient temperature: < ±0.14 % (relative to full scale value)
Resolution16 bit, representation adjustable: 0.1/0.01 °C or 1/2/4 µV per digit
Input filter limit frequencytyp. 1 kHz
Conversion timeapprox. 2.5 s up to 20 ms, depending on configuration and filter setting, default: approx. 250 ms
Distributed clocks
Power supplyvia the E-bus
Current consumption E-bustyp. 200 mA
Current consumption power contacts
Electrical isolation500 V (E-bus/signal voltage)
Special featureschannel by channel wire break detection, internal and external cold junction, firmware filter adjustable
Weightapprox. 60 g
Operating/storage temperature-25…+60 °C/-40…+85 °C
Relative humidity95 %, no condensation
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos.IP20/variable
Approvals/markingsCE, UL, ATEX, IECEx, cFMus
Ex markingATEX:
II 3 G Ex nA IIC T4 Gc
IECEx:
Ex nA IIC T4 Gc
Ex tc IIIC T135 °C Dc
cFMus:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx ec IIC T4 Gc

Housing dataEL-12-8pin
Design formcompact terminal housing with signal LEDs
Materialpolycarbonate
Dimensions (W x H x D)12 mm x 100 mm x 68 mm
Installationon 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means ofdouble slot and key connection
Markinglabeling of the BZxxx series
Wiringsolid conductor (e), flexible conductor (f) and ferrule (a): spring actuation by screwdriver
Connection cross-sections*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm²
Connection cross-section AWGs*: AWG 28…14,
st*: AWG 28…14,
f*: AWG 26…16
Stripping length8…9 mm
Current load power contactsImax: 10 A

*s: solid wire; st: stranded wire; f: with ferrule