Description
The analog EL3356 input terminal enables direct connection of a resistor bridge or load cell in a 4- or 6-wire connection technology. The ratio between the bridge voltage UD and the supply voltage UREF is determined simultaneously in the input circuit and the final load value is calculated as a process value on the basis of the settings in the terminal. With automatic self-calibration (can be deactivated) and dynamic filters the terminal with measuring cycles of 10 ms can be used for slow weighings with high precision.
Technical data | EL3356 |
---|---|
Number of inputs | 2, for 1 resistor bridge in full bridge technology |
Power supply | via the E-bus |
Technology | resistor bridge, strain gauge |
Signal type | differential |
Distributed clocks | – |
Measuring range UD | max. ±27 mV |
Measuring range UREF | max. ±13.8 V |
Internal resistance | > 200 kΩ (UREF), > 1 MΩ (UD) |
Input filter limit frequency | 10 kHz low pass (-3 dB) |
Conversion rate | 100…4 samples/s (10…250 ms conversion time) |
Power supply UV | up to 12 V DC from power contacts, dependent on sensor |
Resolution | 16 bit, 32 bit presentation |
Measurement error/ uncertainty | < ±0.01 % for the calculated load value in relation to the final load value with a 12 V feed and 24 mV bridge voltage (hence nominal strain gauge characteristic value of 2 mV/V), self-calibration active, 50 Hz filter active |
Current consumption power contacts | depends on strain gauge supply, min. 1 mA |
Current consumption E-bus | typ. 210 mA |
Supported nominal sensitivity | all, parameter resolution: 0.01 µV/V; recommended: 0.5…4 mV/V |
Special features | self-calibration, quadruple averager, dynamic filters |
Weight | approx. 60 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Pluggable wiring | for all ESxxxx terminals |
Approvals/markings | CE, UL, ATEX, IECEx |
Ex marking | ATEX: II 3 G Ex nA IIC T4 Gc IECEx: Ex ec IIC T4 Gc |
Housing data | EL-12-8pin | ES-12-8pin |
---|---|---|
Design form | compact terminal housing with signal LEDs | terminal housing with pluggable wiring level |
Material | polycarbonate | |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm | |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock | |
Side by side mounting by means of | double slot and key connection | |
Marking | labeling of the BZxxx series | |
Wiring | solid conductor (e), flexible conductor (f) and ferrule (a): spring actuation by screwdriver | |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² | s*: 0.08…1.5 mm², st*: 0.08…1.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG 28…14, st*: AWG 28…14, f*: AWG 26…16 | s*: AWG 28…16, st*: AWG 28…16, f*: AWG 26…16 |
Stripping length | 8…9 mm | 9…10 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule
MANUFACTURERS
Price history
As soon as the price of the products decreases, you will immediately know about it.
The price has not changed yet. We will show it on this chart once it changes