Description
The EL9410 power supply terminal is used to refresh the E-bus. Data is exchanged between the coupler and the EtherCAT Terminal over the E-bus. Each terminal draws a certain amount of current from the E-bus (see “current consumption E-bus” in the technical data). This current is fed into the E-bus by the relevant coupler’s power supply unit. In configurations with a large number of terminals it is possible to use the EL9410 in order to supply an extra 2 A to the E-bus. The EL9410 has a diagnostic function which is displayed by LED and on the process image.
Technical data | EL9410, ES9410 |
---|---|
Technology | power supply terminal |
Short-circuit proof | yes |
Input voltage | 24 V DC (-15 %/+20 %) |
Input current | typ. 70 mA + (E-bus/4) |
Output voltage | 5 V for E-bus supply |
Output current | 2 A |
Current consumption E-bus | – |
Electrical isolation | 500 V (E-bus/field potential) |
Power contacts | max. 24 V DC/max. 10 A |
Diagnostics in the process image | yes |
Special features | standard EL supply |
Weight | approx. 65 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. rating/installation pos. | IP20/variable |
Pluggable wiring | for all ESxxxx terminals |
Approvals/markings | CE, UL, ATEX |
Ex marking | II 3 G Ex nA IIC T4 Gc |
Housing data | EL-12-8pin |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | labeling of the BZxxx series |
Wiring | solid conductor (e), flexible conductor (f) and ferrule (a): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG 28…14, st*: AWG 28…14, f*: AWG 26…16 |
Stripping length | 8…9 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule
Features
Source:
Source:MANUFACTURER NETWORK
MANUFACTURERS
Price history
As soon as the price of the products decreases, you will immediately know about it.
The price has not changed yet. We will show it on this chart once it changes