Description
The EP2328-0002 EtherCAT Box combines four digital inputs (two M12 sockets at the top) and four digital outputs (two M12 sockets at the bottom) in one device. The inputs have a filter of 3.0 ms. The outputs process load currents up to 2.0 A, are short-circuit-proof and protected against reverse polarity. The signal status is indicated by LED. The signals are connected via M12 screw type connectors. Two channels are available per M12 socket. The total current of all outputs is limited to 4 A.
The connected sensors are supplied via an internal, short-circuit-proof driver module with a total of 0.5 A for all sensors. The outputs are supplied via UP. All outputs are short-circuit-proof and protected against reverse polarity.
Technical data | EP2328-0002 |
---|---|
Protocol | EtherCAT |
Bus interface | 2 x M8 socket, shielded, screw type |
Specification | EN 61131-2, type 1/3 |
Number of channels | 4 inputs + 4 outputs |
Input/output connections | M12, screw type |
Input filter | 3.0 ms |
“0” signal voltage | -3…+5 V |
“1” signal voltage | 11…30 V, 6 mA input current (EN 61131-2, type 3) |
Sensor supply | from control voltage, max. 0.5 A, short-circuit proof in total |
Load type | ohmic, inductive, lamp load |
Rated load voltage | 24 V DC (-15 %/+20 %) |
Max. output current | 2 A per channel, individually short-circuit proof, ∑ 4 A |
Switching times | typ. TON: 200 µs, typ. TOFF: 200 µs |
Short-circuit current | typ. 15 A |
Auxiliary power current | typ. 20 mA |
Current consumption from US | typ. 120 mA |
Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
Electrical isolation | 500 V |
Weight | approx. 165 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Approvals/markings | CE, UL, ATEX |
Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
Ex marking | II 3 G Ex nA IIC T4 Gc |
Technical data | EP2328-0002 |
---|---|
Protocol | EtherCAT |
Bus interface | 2 x M8 socket, shielded, screw type |
Specification | EN 61131-2, type 1/3 |
Number of channels | 4 inputs + 4 outputs |
Input/output connections | M12, screw type |
Input filter | 3.0 ms |
“0” signal voltage | -3…+5 V |
“1” signal voltage | 11…30 V, 6 mA input current (EN 61131-2, type 3) |
Sensor supply | from control voltage, max. 0.5 A, short-circuit proof in total |
Load type | ohmic, inductive, lamp load |
Rated load voltage | 24 V DC (-15 %/+20 %) |
Max. output current | 2 A per channel, individually short-circuit proof, ∑ 4 A |
Switching times | typ. TON: 200 µs, typ. TOFF: 200 µs |
Short-circuit current | typ. 15 A |
Auxiliary power current | typ. 20 mA |
Current consumption from US | typ. 120 mA |
Power supply connection | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
Electrical isolation | 500 V |
Weight | approx. 165 g |
Operating/storage temperature | -25…+60 °C/-40…+85 °C |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Approvals/markings | CE, UL, ATEX |
Protect. rating/installation pos. | IP65/66/67 (conforms to EN 60529)/variable |
Ex marking | II 3 G Ex nA IIC T4 Gc |
Housing data | 8 x M8, 4 x M12 |
---|---|
Dimensions (W x H x D) | 30 mm x 126 mm x 26.5 mm |
Material | PA6 (polyamide) |
Installation | 2 fixing holes 3.5 mm diameter for M3 |
Features
MANUFACTURERS
Price history
The price has not changed yet. We will show it on this chart once it changes