Description
The Honeywell R7847A1033 STANDARD. 3S FFRT. RECOMMENDED FOR CYCLED HEATING EQUIPMENT. USE WITH Flame ROD, PHOTO- CELL, OR C7012A,C.
Overview
Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules.
Features
- Flame failure response time of 0.8 or 3.0 seconds.
- Flame signal strength ranges from 0.0 to 5.0 Vdc.
- Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
- Flame signal test jacks to measure amplifier flame signal voltage.
- Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
- Compatible with existing Honeywell flame detectors (order separately).
Product Specifications
Comments | Color: Green |
Approvals, Underwriters Laboratories Inc. | Listed: File No. MP268, Guide No. MCCZ |
Approvals, Canadian Standards Association | Certified: File No. LR95329-3 |
Customer Special | |
Flame Failure Response Time (sec) | 2.0 sec or 3.0 sec |
Approvals, Control Safety Devices | |
Approvals, Swiss RE | Acceptable |
Approvals, Factory Mutual | Approved: Report No. 1V9A0.AF |
Self Checking | None (standard) |
Use With Primary Safety Control | 7800 SERIES Relay Modules |
Use With Flame Sensor | Gas: Rectifying Flame Rods C7004, C7005, C7007, C7008, C7009, Q179; Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C |