Description
R7851C1008 self-check flame amplifier 2 or 3 second. For 7800 and R7140 relay; Flame Signal Amplifier, 2 Second or 3 Second Flame Failure Response Time, Dynamic Self Check, Gas, Oil, Coal: Optical (UV Only ) Flame Sensor C7961E and C7961F, Use with 7800 Series Primary Safety Control, Color: White, Flame Signal Strength Ranges from 0.0-5 Vdc
The Honeywell R7851C1008 dynamic flame amplifier
Overview
Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules.
Features
- Flame failure response time of 0.8 or 3.0 seconds.
- Flame signal strength ranges from 0.0 to 5.0 Vdc.
- Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
- Flame signal test jacks to measure amplifier flame signal voltage.
- Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
- Compatible with existing Honeywell flame detectors (order separately).
Product Specifications
Comments | Color: White |
Approvals, Underwriters Laboratories Inc. | Listed: File No. MP268, Guide No. MCCZ |
Approvals, Canadian Standards Association | Certified: File No. LR95329-3 |
Flame Failure Response Time (sec) | 0 sec or 3.0 sec |
Approvals, Swiss RE | Acceptable |
Approvals, Factory Mutual | Approved: Report No. 1V9A0.AF |
Self Checking | Dynamic Self-Check |
Use With Primary Safety Control | 7800 SERIES Relay Modules |
Use With Flame Sensor | Gas, oil, coal: optical (UV only) C7961E,F |