Description
Flame Signal Amplifier, 2 Second or 3 Second Flame Failure Response Time, Dynamic Self Check, Gas,Oil, Coal: Ultraviolet Flame Sensor C7061, Use with 7800 Series Primary Safety Control, Color: Purple, Flame Signal Strength Ranges from 0.0-5 Vdc
The Honeywell R7861A1026 Amplifier FOR USE WITH RM78XX AND EX78XX Relay Modules, 50/60HZ, 2 OR 3 SEC Flame FAILURE RESPONSE TIME.
Overview
Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame when used with 7800 SERIES relay modules.
Features
- Flame failure response time of 0.8 or 3.0 seconds.
- Flame signal strength ranges from 0.0 to 5.0 Vdc.
- Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
- Flame signal test jacks to measure amplifier flame signal voltage.
- Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
- Compatible with existing Honeywell flame detectors (order separately).
Product Specifications
Comments | Color: Purple |
Approvals, Underwriters Laboratories Inc. | Listed: File No. MP268, Guide No. MCCZ |
Approvals, Canadian Standards Association | Certified: File No. LR95329-3 |
Flame Failure Response Time (sec) | 2.0 sec or 3.0 sec |
Approvals, Swiss RE | Acceptable |
Approvals, Factory Mutual | Approved: Report No. 1V9A0.AF |
Self Checking | Dynamic Self-Check |
Use With Primary Safety Control | 7800 SERIES Relay Modules |
Use With Flame Sensor | Gas, oil, coal: Ultraviolet Flame Sensor C7061 |