- For applications in hazardous areas
- Reliable non-contact monitoring of the rotational speed with regard to underspeed
- 2 in 1: speed sensor and evaluation in one compact housing
- Easy setting of the switch point via potentiometer
- For direct connection to a PLC
Output function | normally open |
---|
Sensing range [mm] | 10 |
---|
Dimensions [mm] | M30 x 1.5 / L = 80 |
---|
Application
Application | simple evaluation of rotating and linear movement with regard to underspeed; blocking |
---|
Electrical data
Nominal voltage AC [V] | 20...250 |
---|
Nominal voltage DC [V] | 20...250 |
---|
Nominal frequency AC [Hz] | 45...65 |
---|
Protection class | II |
---|
Reverse polarity protection | yes |
---|
Outputs
Total number of outputs | 1 |
---|
Output function | normally open |
---|
Max. voltage drop switching output DC [V] | 7.5 |
---|
Minimum load current [mA] | 6 |
---|
Max. leakage current [mA] | 1.5 |
---|
Permanent current rating of switching output AC [mA] | 200 |
---|
Permanent current rating of switching output DC [mA] | 100 |
---|
Short-time current rating of switching output [mA] | 2200; (20 ms / 0,5 Hz) |
---|
Short-circuit proof | no |
---|
Overload protection | no |
---|
Detection zone
Sensing range [mm] | 10 |
---|
Sensing range adjustable | no |
---|
Real sensing range Sr [mm] | 10 ± 10 >#/td### |
---|
Operating distance [mm] | 0...8.1 |
---|
Measuring/setting range
Setting range [Imp/min] | 5...3600 |
---|
Accuracy / deviations
Correction factor | steel: 1 / stainless steel: 0.8 / brass: 0.5 / aluminium: 0.5 / copper: 0.4 |
---|
Hysteresis [% of Sr] | 10 |
---|
Response times
Start-up delay [s] | 12 |
---|
Max. damping frequency [Imp/min] | 4800 |
---|
Software / programming
Adjustment of the switch point | multiturn potentiometer |
---|
Operating conditions
Ambient temperature [°C] | -20...60 |
---|
Storage temperature [°C] | -25...60 |
---|
Protection | IP 65; IP 67 |
---|
Tests / approvals
Approval | IECEx BVS 17.0094X |
---|
ATEX marking | II 3D Ex tc IIIC T80°C Dc X |
---|
EMC | |
---|
MTTF [years] | 491 |
---|
Mechanical data
Weight [g] | 314 |
---|
Mounting | flush mountable |
---|
Dimensions [mm] | M30 x 1.5 / L = 80 |
---|
Thread designation | M30 x 1.5 |
---|
Materials | brass special coating; PA; TPE-U |
---|
Displays / operating elements
Display | switching status | 2 x LED, yellow |
|
---|
Electrical connection
Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting; Place the fuse outside the hazardous area. |
---|
Accessories
Remarks
Remarks | Recommendation Check the safe functioning of the unit after a short circuit. |
|
---|
Electrical connection
Connection | Cable: 2 m, PUR; 2 x 0.5 mm² |
---|
ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — EN-GB — DI103A — 24.04.2023 —