- Reliable detection of system pressure in industrial applications
- High shock and vibration resistance
- Excellent repeatability and low linearity error
- Lifespan of more than 50 million pressure cycles
- Compact and robust stainless steel housing for use where space is restricted
Product characteristics
Number of inputs and outputs | Number of analog outputs: 1 |
---|
Measuring range | 0...400 bar | 0...5800 psi | 0...40 MPa |
|
---|
Process connection | threaded connection G 1/4 external thread |
---|
Application
Application | for industrial applications |
---|
Media | liquids and gases |
---|
Medium temperature [°C] | -25...90 |
---|
Min. bursting pressure | |
---|
Pressure rating | |
---|
Type of pressure | relative pressure |
---|
Electrical data
Operating voltage [V] | 16...36 DC |
---|
Current consumption [mA] | < 6 |
---|
Min. insulation resistance [MΩ] | 100; (500 V DC) |
---|
Protection class | III |
---|
Reverse polarity protection | yes |
---|
Inputs / outputs
Number of inputs and outputs | Number of analog outputs: 1 |
---|
Outputs
Total number of outputs | 1 |
---|
Output signal | analog signal |
---|
Number of analog outputs | 1 |
---|
Analog voltage output [V] | 0...10 |
---|
Min. load resistance [Ω] | 2000 |
---|
Measuring/setting range
Measuring range | 0...400 bar | 0...5800 psi | 0...40 MPa |
|
---|
Accuracy / deviations
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
---|
Characteristics deviation [% of the span] | < ± 1,0; (incl. drift due to tightening torque, zero and span error) |
---|
Linearity deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS) |
---|
Hysteresis deviation [% of the span] | < ± 0,2 |
---|
Long-term stability [% of the span] | < ± 0,1; (per 6 months) |
---|
Temperature coefficient zero point [% of the span / 10 K] | < ± 0,1; (-25...90 °C) |
---|
Temperature coefficient span [% of the span / 10 K] | < ± 0,1; (-25...90 °C) |
---|
Reaction times
Step response time analog output [ms] | 3 |
---|
Operating conditions
Ambient temperature [°C] | -25...90 |
---|
Storage temperature [°C] | -40...100 |
---|
Protection | IP 67; IP 69K |
---|
Tests / approvals
EMC | EN 61000-4-2 ESD | 4 kV CD / 8 kV AD | EN 61000-4-3 HF radiated | 10 V/m | EN 61000-4-4 Burst | 4 kV coupling clamp | EN 61000-4-5 Surge | 1 kV signal for DC units | EN 61000-4-6 HF conducted | 10 V |
|
---|
Shock resistance | DIN IEC 68-2-27 | 50 g (11 ms) |
|
---|
Vibration resistance | DIN IEC 68-2-6 | 20 g (10...2000 Hz) |
|
---|
MTTF [years] | 1116 |
---|
Pressure equipment directive | sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
---|
Mechanical data
>th >Restrictor element integrated
Weight [g] | 83 |
---|
Material | stainless steel (1.4404 / 316L); PA |
---|
Materials (wetted parts) | stainless steel (1.4404 / 316L); FKM |
---|
Min. pressure cycles | 50 million |
---|
Process connection | |
---|
no (can be retrofitted) |
Remarks
Remarks | BFSL = Best Fit Straight Line | LS = limit value setting |
|
---|
Pack quantity | 1 pcs. |
---|
Electrical connection
Connection | Connector: 1 x M12; coding: A |
---|
ifm efector, inc. • 1100 Atwater Drive • Malvern • PA 19355 — We reserve the right to make technical alterations without prior notice. — EN-US — PT9540-01 — 29.04.2014 —