Model | GC-1000R | |
Input/output points | Safety inputs | 14 |
Safety outputs | 4 | |
Safety relay output | 1 (3a) | |
AUX outputs | 4 | |
Test outputs | ||
Maximum number of connectable expansion units | - | |
Maximum number of connectable remote I/O modules | ||
GC-Link ports | 2 ports | |
Safety input specifications | Input device | Contact output device or PNP output device |
Input type | Type3 | |
ON level (voltage/current) | Min. 11 V/2 mA | |
OFF level (voltage/current) | Max. 5 V/1.5 mA | |
Short-circuit current | Si 0 to 3: Approx. 5 mA | |
Protection circuit | Surge protection circuit, wrong wiring protection circuit | |
Maximum cable length | Max. 100 m 328.1' | |
Safety output specifications | Output type | PNP transistor output (DC-13, Type 0.5, Protected outputs)*1 |
Maximum load current | 500 mA | |
Residual voltage (during ON) | Max. 2.0 V | |
Leakage current (during OFF) | Max. 0.5mA | |
Maximum capacitive load | 0.5 µF | |
Load wiring resistance | Max. 2.5Ω | |
Protection circuit | Overcurrent protection circuit, reverse connection protection circuit | |
Maximum cable length | Max. 30 m 98.4' | |
Safety relay output specifications | Output type | Relay (3a) (Externally-protected outputs)*2 |
Rated load (resistance load) | 250 VAC 6A / 30 VDC 6A*3 | |
Rated load (inductive load) | 240 VAC 2A (AC-15) / 24 VDC 1A (DC-13) | |
Relay output mechanical life | Resistance load (250 VAC 6A/30 VDC 6A): Min. 100,000 times | |
Maximum cable length | Max. 100 m 328.1' | |
B10d | With rated load: 400,000 times | |
Test output specifications | Output type | PNP transistor output*4 |
Maximum load current | 100 mA | |
Protection circuit | Overcurrent protection circuit, reverse connection protection circuit | |
Maximum cable length | Max. 100 m 328.1'*5 | |
AUX output specifications | Output type | Transistor output (PNP/NPN selectable by wiring) |
Maximum load current | PNP: 100 mA, NPN: 20 mA | |
Residual voltage (during ON) | Max. 2.0 V | |
Leakage current (during OFF) | Max. 0.5 mA | |
Protection circuit | Overcurrent protection circuit, reverse connection protection circuit | |
Maximum cable length | Max. 30 m 98.4' | |
Communication interface | USB | USB2.0 |
Ethernet | - | |
Network functionality | ||
Others | LCD display | 1.77-inch color LCD |
Display buttons | 4 points (3 operation keys + 1 BACK key) | |
Applicable standards | EMC | EMS: IEC 61131-2/-6, EN61131-2/-6 |
Safety | IEC 61508, EN 61508 SIL3 | |
Dimensions | 85×95×90 mm 3.35"×3.74"×3.54" (W×D×H) | |
Power supply | Power voltage | 24 VDC (-20 to +20%) Class 2 |
Power consumption | Max. 200 mA | |
Environmental resistance | Ambient temperature | −10 to +55 °C 14 to 131 °F (No freezing) |
Storage temperature | −25 to +70 °C -13 to 158 °F (No freezing) | |
Relative humidity | 5 to 85% (No condensation) | |
Operating altitude | Max. 2000 m 6561.7' | |
Overvoltage category | II | |
Pollution degree | 2 | |
Vibration resistance | Frequency: 5 to 9 Hz, Half amplitude: 3.5 mm 0.14" | |
Shock resistance | Acceleration: 150 m/s2, Operating time: 11 ms, 3 times each in X, Y, Z directions | |
Material | Polycarbonate | |
Weight | Approx. 360 g | |
*1 Paragraph 6.4.6 Temporary overload of IEC 61131-2 supports up to 1.2 times the maximum load current. |