Description
Power rating | 240 W |
---|---|
Output voltage | 24 VDC |
Rated input voltage | 100 to 240 VAC |
Construction | Covered type |
Connection | Terminal blocks |
Terminal type | Push-In Plus Terminal Block |
Efficiency | 91 % typ. (at 115 VAC input) 93 % typ. (at 230 VAC input) | |
---|---|---|
Input | ||
Allowable input voltage variable range | 85 to 264 VAC (Single-phase)/265 to 300 VAC (1 s) 90 to 350 VDC | |
Frequency | 50/60Hz (47 to 63 Hz) | |
Rated input current | 2.4 A typ. (at 115 VAC input) 1.3 A typ. (at 230 VAC input) | |
Power factor | 0.9 min. | |
Leakage current | 0.5 mA max. (at 115 VAC input) 1 mA max. (at 230 VAC input) | |
Inrush current (cold start at 25 ℃) | 16 A typ. (at 115 VAC input) 32 A typ. (at 230 VAC input) | |
Output | Rated output current | 10 A |
Output voltage variable range | 21.6 to 28 V With V.ADJ | |
Rated output power | 240 W | |
Maximum peak current | 15 A | |
Ripple | 100 mV(p-p) max. | |
Static input variation influence | 0.5 % max. | |
Static load variation influence | 1.5 % max. | |
Ambient temperature variation influence | 0.05 %/℃ max. | |
Start up time | 1000 ms max. (at 115 VAC input) 1000 ms max. (at 230 VAC input) | |
Hold time | 35 ms typ. (at 115 VAC input) 35 ms typ. (at 230 VAC input) | |
Additional functions | Overload protection | Yes, automatic reset |
Overvoltage protection | Yes, Shut off the input voltage and turn on the input again | |
Series operation | Yes (Up to 2 Power Supplies with external diode) | |
Parallel operation | Yes (Up to 2 Power Supplies) | |
Output indicator | Yes (color: green) | |
Undervoltage alarm | Output: Yes (photoswitch output, 30 VDC max., 50 mA max.) | |
Insulation | Dielectric strength | Between all input terminals and all output terminals: 3 kVAC for 1 min, Cut-off current: 20 mA Between all input terminals and PE terminals: 2 kVAC for 1 min, Cut-off current: 20 mA Between all output terminals and PE terminals: 1 kVAC for 1 min, Cut-off current: 20 mA Between all output terminals and all low-voltage detection output terminals: 500 VAC for 1 min, Cut-off current: 10 mA |
Insulation resistance | Between all output terminals/all low-voltage detection output terminals and all input terminals/PE terminals: 100 MΩ min., at 500 VDC | |
Environment | Vibration resistance | 10 to 55 Hz, 5 G max., 0.42 mm single amplitude in each 3 directions for 2 hours |
Shock resistance | 150 m/s2, in each 6 directions 3 times | |
Altitude | 3000 m max. | |
Ambient temperature (Operating) | -40 to 70 ℃ (with no freezing or condensation) | |
Ambient temperature (Storage) | -40 to 85 ℃ (with no freezing or condensation) | |
Ambient humidity (Operating) | 95 %RH max. | |
Ambient humidity (Storage) | 95 %RH max. | |
Reliability | MTBF | 135,000 hours min. |
Life expectancy | 10 years min. (at rated input, a load rate of 50% load, under the temperature of 40 ℃ max., standard mounting) | |
Construction | Construction | Covered type |
Connection | Terminal blocks | |
Terminal type | Push-In Plus Terminal Block | |
Mounting | DIN track mounting | |
Coationg | Yes | |
Degree of protection | IP20, EN/IEC 60529 | |
Weight (Main) | 700 g max. |