Description
Power rating | 480 W |
---|---|
Output voltage | 24 VDC |
Rated input voltage | 380 to 480 VAC (Three-phase / two-phase) 450 to 600 VDC |
Construction | Covered type |
Connection | Terminal blocks |
Terminal type | Rod terminal |
Power rating | 480 W | |
---|---|---|
Output voltage | 24 VDC | |
Efficiency | 93 % typ. (Three-phase 400 VAC input) | |
Input | Rated input voltage | 380 to 480 VAC (Three-phase / two-phase) 450 to 600 VDC |
Allowable input voltage variable range | 340 to 576 VAC (Two-phase)/320 to 576 VAC (Three-phase) 450 to 810 VDC | |
Frequency | 50/60Hz (47 to 63 Hz) | |
Rated input current | 0.8 A typ. (Three-phase 400 VAC input) | |
Leakage current | 3.5 mA max., 1.0 mA typ. (Three-phase 400 VAC input) | |
Inrush current (cold start at 25 ℃) | 4 A typ. (Three-phase 400 VAC input) | |
Output | Rated output current | 20 A |
Output voltage variable range | 24 to 29.5 VDC With V.ADJ | |
Maximum peak current | 24 A | |
Ripple | 30 mV(p-p) max. | |
Static input variation influence | 0.5 % max. | |
Static load variation influence | 1.5 % max. | |
Ambient temperature variation influence | 0.05 %/℃ max. | |
Start up time | 500 ms typ. (Three-phase 400 VAC input) | |
Hold time | 40 ms typ. (Three-phase 400 VAC input) | |
Additional functions | Overload protection | Yes, automatic reset |
Overvoltage protection | Yes, Shut off the input voltage and turn on the input again | |
Series operation | Yes (Up to 2 Power Supplies with external diode) | |
Parallel operation | Yes (Up to 2 Power Supplies) | |
Output indicator | Yes (LED, color: green, lighting from 80 to 90% or more of rated voltage) | |
Insulation | Dielectric strength | Between all input terminals and all output terminals: 3 kVAC for 1 min, Cut-off current: 20 mA Between all input terminals and PE terminals: 2.5 kVAC for 1 min, Cut-off current: 20 mA Between all output terminals and PE terminals: 1 kVAC for 1 min, Cut-off current: 30 mA |
Insulation resistance | Between all output terminals and all input terminals/ PE terminals: 100 MΩ min., at 500 VDC | |
Environment | Vibration resistance | 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours |
Shock resistance | 150 m/s2, in each 6 directions 3 times | |
Ambient temperature (Operating) | -40 to 70 ℃ (with no freezing or condensation) | |
Ambient temperature (Storage) | -40 to 85 ℃ (with no freezing or condensation) | |
Ambient humidity (Operating) | 95 %RH max. | |
Ambient humidity (Storage) | 95 %RH max. | |
Reliability | MTBF | 135,000 hours min. |
Construction | Construction | Covered type |
Connection | Terminal blocks | |
Terminal type | Rod terminal | |
Mounting | DIN track mounting | |
Degree of protection | IP20, EN/IEC 60529 | |
Weight (Main) | 1400 g max. |
Note
Do not use the Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.
As of March 14, 202
MANUFACTURERS
Price history
As soon as the price of the products decreases, you will immediately know about it.
The price has not changed yet. We will show it on this chart once it changes