Description
-New modern look & feel of all machines
-Designed to meet the requirements of industrial and HVAC applications
-Easier to install and operate with multi-standard screws
-With IEC60335-1 compliance, improved fire resistance, and dustproof auxiliaries
Description
TeSys D contactors have a variety of accessories that can be mount to them. This on delay timer attachemnt mounts on the top of contactor with rating from 9 amp to 150 amp. The one NO and one NC contacts can be used in the control circuit. TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for any type of application. TeSys D contactors offer quick simple setup, while maintaining a compact size. Contactors have both horsepower and Kw motor rating for international acceptance. An extennsive line of accessories makes it easy to meet the requirements of most applications. These contactors have UL, CSA, GOST, RINA, BV, CCC, DNV, GL, LROS certifications.
Range | TeSys TeSys Deca |
---|---|
Product name | TeSys Deca |
Product or Component Type | Time delay auxiliary contact block |
Range compatibility | TeSys Deca CAD TeSys Deca LC1D TeSys F LC1F TeSys F CR1F |
Mounting Location | Front |
Pole contact composition | 1 NO + 1 NC |
Contacts operation | Time delay |
Timer type | On delay |
Time delay range | 1...30 s |
[Ue] rated operational voltage | 690 V AC 25...400 Hz |
[Ie] rated operational current | 6 A at 120 V AC-15 1.04 A at 690 V AC-15 0.55 A at 125 V DC-13 0.1 A at 600 V DC-13 |
[Ui] rated insulation voltage | 690 V IEC 60947-5-1 600 V UL 60947-5-1 600 V CSA C22.2 No 60947-5-1 |
[Ith] conventional free air thermal current | 10 A (at 140 °F (60 °C)) |
Standards | CSA C22.2 No 60947-5-1 GB/T 14048.5 EN/IEC 60947-5-1 |
Product Certifications | IECEE CB Scheme br>CSA CCC EAC UKCA |
Complementary
Irms rated making capacity | 140 A at <= 690 V AC conforming to IEC 60947-5-1 250 A at <= 690 V DC conforming to IEC 60947-5-1 |
---|---|
Permissible short-time rating | 100 A 140 °F (60 °C) 1 s 120 A 140 °F (60 °C) 500 ms 140 A 140 °F (60 °C) 100 ms |
Protection type | GG fuse 10 A |
Mechanical durability | 5 Mcycles |
Minimum switching current | 5 mA |
Minimum switching voltage | 17 V |
Non-overlap time | 1.5 ms on de-energisation no overlap between NC and NO contact 1.5 ms on energisation no overlap between NC and NO contact |
Insulation resistance | > 10 MOhm |
Connections - terminals | Screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)flexible with cable end screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)flexible without cable end screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible without cable end screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²)rigid screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)rigid screw clamp terminals |
Tightening torque | 15.05 lbf.in (1.7 N.m) flat Ø 6 mm 15.05 lbf.in (1.7 N.m) Philips No 2 15.05 lbf.in (1.7 N.m) pozidriv No 2 |
Height | 1.89 in (48 mm) |
Width | 1.73 in (44 mm) |
Depth | 2.40 in (61 mm) |
color | Dark grey |
Environment>th >Ambient Air Temperature for Storage
Environmental characteristic | Normal environment |
---|---|
IP degree of protection | IP20 conforming to IEC 60529 |
Protective treatment | |
-76…176 °F (-60…80 °C) | |
Ambient Air Temperature for Operation | -40…158 °F (-40…70 °C) |
Operating altitude | 9842.52 ft (3000 m) |
Ordering and shipping details
Category | 22341-CONTACTOR,D,K,&F ACCESS |
---|---|
Discount Schedule | I12 |
GTIN | 3389110385892 |
Returnability | Yes |
Country of origin | FR |
Packing Units
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 2.05 in (5.2 cm) |
Package 1 Width | 2.56 in (6.5 cm) |
Package 1 Length | 1.97 in (5 cm) |
Package 1 Weight | 2.61 oz (74 g) |
MANUFACTURERS
Price history
The price has not changed yet. We will show it on this chart once it changes