Free shipping

Telemecanique GV3-ME40 (Canceled, replaced by GV3P40) Motor Circuit Breaker 25-40A

Brand:SCHNEIDER ELECTRIC, Condition:new
$150.00

Order today and receive in 4 weeks (pay when ready):

$0.00

GV3-ME40
PREORDER (Available On: 11/06/2024)
+

Description

Main

rangeTeSys
product nameTeSys GV3
device short nameThermal magnetic circuit breaker
product or component typeCircuit breaker
device applicationMotor
poles description3P
network typeAC
control typePush-button
motor power kW15 kW at 400...415 V AC 50/60 Hz
22 kW at 500 V AC 50/60 Hz
22 kW at 660...690 V AC 50/60 Hz
30 kW at 660...690 V AC 50/60 Hz
18.5 kW at 400...415 V AC 50/60 Hz
18.5 kW at 500 V AC 50/60 Hz
trip unit technologyThermal-magnetic
utilisation categoryAC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
connections - terminalsPower circuit: screw clamp terminal 1 cable(s) 2.5…35 mm²solid
Power circuit: screw clamp terminal 1 cable(s) 2.5 mm²flexible without cable end
Power circuit: screw clamp terminal 2 cable(s) 16 mm²flexible with cable end

Complementary

network frequency50/60 Hz
mounting modeFixed
mounting supportPlate
Rail
mounting positionVertical
Horizontal
thermal protection adjustment range25…40 A conforming to IEC 60947-4-1
phase failure sensitivityYes conforming to IEC 60947-4-1 § 7-2-1-5-2
[Ue] rated operational voltage600 V AC 50/60 Hz conforming to UL 508
690 V AC 50/60 Hz conforming to IEC 60947-2
600 V AC 50/60 Hz conforming to CSA C22.2 No 14
[Ui] rated insulation voltage690 V conforming to IEC 60947-2
[Ith] conventional free air thermal current40 A conforming to IEC 60947-4-1
network frequency50/60 Hz conforming to CSA
50/60 Hz conforming to IEC 60947-4-1
50/60 Hz conforming to UL
[Uimp] rated impulse withstand voltage6 kV IEC 60947-2
power dissipation per pole8 W
mechanical durability30000 cycles
electrical durability30000 cycles for AC-3 at 440 V In/2
maximum number of switchings25 cyc/h
rated dutyContinuous conforming to IEC 60947-4-1
tightening torque5 N.m - on EverLink BTR screw connectors - cable 2.5…16 mm²
5 N.m - on EverLink BTR screw connectors - cable 2.5…3.5 mm²
breaking capacity10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 230...240 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
2 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % at 230...240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
60 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
height120 mm
width61 mm
depth113 mm
net weight0.7 kg

Environment

standardsNF EN
IEC 60947-2
DIN EN 60947-2
EN 60947-4-1
EN 60947-2
BS EN
DIN EN 60947-4-1
IEC 60947-4-1
product certificationsCSA
LROS (Lloyds register of shipping)
UL
protective treatmentTC
IP degree of protectionIP20 conforming to IEC 60529 (open mounted)
IP55 conforming to IEC 60529 (in enclosure)
shock resistance22 gn 20 ms conforming to IEC 60068-2-27
vibration resistance2.5 gn (f= 0…25 Hz) conforming to IEC 60068-2-6
ambient air temperature for operation-20…40 °C in enclosure
-20…60 °C open mounted
ambient air temperature for storage-40…80 °C
fire resistance960 °C conforming to IEC 60695-2-1
operating altitude<= 3000 m
resistance to mechanical impact0.5 J

Packing Units

Package 1 Weight0.743 kg
Package 1 Height1.300 dm
Package 1 width1.330 dm
Package 1 Length0.680 dm

Offer Sustainability

EU RoHS DirectiveCompliant
EU RoHS Declaration
Mercury freeYes
RoHS exemption informationYes
China RoHS RegulationChina RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
WEEEThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Contractual warranty