- 6 digital outputs
- Relay module for 115 VAC
- 6 normally open contacts
- Single-channel isolated outputs
The module is equipped with 6 relay outputs.
General information
B&R ID code | 0x2019 |
Status indicators | I/O function per channel, operating state, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
Outputs | Yes, using LED status indicator |
Power consumption | |
Bus | 1.1 W |
Internal I/O | - |
Additional power dissipation caused by actuators (resistive) [W] | +0.45 |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X |
UL | cULus E115267
Industrial control equipment |
HazLoc | cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5 |
DNV | Temperature: B(0 - 55°C)
Humidity: B(up to 100%)
Vibration: B(4 g)
EMC: B(bridge and open deck) |
LR | ENV1 |
KR | Yes |
ABS | Yes |
BV | EC33B
Temperature: 5 - 55°C
Vibration: 4 g
EMC: Bridge and open deck |
EAC | Yes |
KC | Yes |
Digital outputs
Variant | Relay / Normally open contact
Channels single-channel isolated |
Nominal voltage | 30 VDC / 115 VAC |
Max. voltage | 125 VAC |
Switching voltage | Max. 110 VDC / 125 VAC |
Rated frequency | DC / 45 to 63 Hz |
Nominal output current | 1 A at 30 VDC / 0.5 A at 115 VAC |
Total nominal current | 6 A at 30 VDC / 3 A at 115 VAC |
Actuator power supply | External |
Inrush current | Max. 2 A (per channel) |
Contact resistance | 75 mΩ at 6 VDC / 1 A |
Switching delay | |
0 → 1 | ≤4 ms |
1 → 0 | ≤4 ms |
Insulation voltages | |
Channel - Bus | Tested at 1500 VAC |
Channel - Channel | Tested at 1000 VAC |
Service life | |
Electrical | Min. 100 x 10³ ops. |
Mechanical | Min. 50 x 106ops. (3 Hz) |
Switching capacity | |
Minimum | 0.01 mA / 10 mV DC |
Maximum | 30 W / 62.5 VA |
Protective circuit | |
Internal | None |
External | |
AC | RC combination or VDR |
DC | Inverse diode, RC combination or VDR |
Electrical properties
Electrical isolation | Channel isolated from channel, bus and I/O power supply |
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note | Order 1x terminal block X20TB12 separately.
Order 1x bus module X20BM11 separately. |
Pitch | 12.5+0.2mm |