MATERIAL NUMBER:
X20PS3300
DESCRIPTION:
- Feed for X2X Link and internal I/O supply
- Electrical isolation of feed and X2X Link supply
- Redundancy of X2X Link supply possible by operating multiple supply modules simultaneously
The supply module is equipped with a feed for the X2X Link as well as the internal I/O supply.
General information
B&R ID code | 0x1BC0 |
Status indicators | Overload, operating state, module status |
Diagnostics | |
Module run/error | Yes, using LED status indicator and software |
Overload | Yes, using LED status indicator and software |
Power consumption for X2X Link power supply | 1.42 W |
Power consumption | |
Internal I/O | 0.6 W |
Additional power dissipation caused by actuators (resistive) [W] | - |
Certifications | |
CE | Yes |
UKCA | Yes |
ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X |
UL | cULus E115267
Industrial control equipment |
HazLoc | cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5 |
DNV | Temperature: B(0 - 55°C)
Humidity: B(up to 100%)
Vibration: B(4 g)
EMC: B(bridge and open deck) |
LR | ENV1 |
KR | Yes |
ABS | Yes |
EAC | Yes |
KC | Yes |
X2X Link power supply input
Input voltage | 24 VDC -15% / +20>#/td### |
Input current | Max. 0.7 A |
Fuse | Integrated, cannot be replaced |
Reverse polarity protection | Yes |
X2X Link power supply output
Nominal output power | 7 W |
Parallel connection | Yes |
Redundant operation | Yes |
Overload characteristics | Short-circuit proof, temporary overload |
Input I/O power supply
Input voltage | 24 VDC -15% / +20>#/td### |
Fuse | Required line fuse: Max. 10 A, slow-blow |
Reverse polarity protection | No |
Output I/O power supply
Nominal output voltage | 24 VDC |
Behavior on short circuit | Required line fuse |
Permissible contact load | 10 A |
Electrical properties
Electrical isolation | X2X Link supply isolated from X2X Link power supply
I/O supply not isolated from I/O power supply
|
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | |
0 to 2000 m | No limitation |
>2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | -25 to 60°C |
Vertical mounting orientation | -25 to 50°C |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note | Order 1x terminal block X20TB12 separately.
Order 1x power supply bus module X20BM01 separately |
Pitch | 12.5+0.2mm |